Methods / Transformer Short-Circuit
How RokBench checks this
Transformer Secondary Short-Circuit
A screening estimate of bolted fault current at the transformer secondary terminals.
1. What this check does
Estimates the symmetrical bolted three-phase fault current at the transformer secondary terminals and, if you enter one, compares it with the equipment rating.
2. Inputs used
- Transformer kVA, secondary line-to-line voltage, nameplate impedance %Z.
- Optional: available fault level of the source in MVA; equipment interrupting or short-circuit rating in kA.
3. Formulas and assumptions
Full-load current I_FL = kVA × 1000 / (√3 · V)
Infinite bus I_SC = I_FL / (Z% / 100)
Source impedance Zs% = kVA / (MVA_SC × 1000) × 100 on the transformer base
Finite source I_SC = I_FL / ((Z% + Zs%) / 100)
- The infinite-bus result is the upper bound for the transformer alone.
- Source and transformer impedances are added as magnitudes, which assumes similar X/R ratios. This is a screening simplification.
- Nameplate impedance is used as given. Actual impedance may be lower within manufacturing tolerance, which increases fault current.
4. What is NOT checked
- Motor contribution, which can add significantly to fault current on buses with large motor loads.
- Secondary cable and bus impedance downstream of the terminals.
- Asymmetrical current, X/R effects on equipment ratings, single-phase and ground faults.
- Arc-flash incident energy and protective device coordination.
5. Reference standards
- NEC 2023 110.9, 110.10 — interrupting rating and circuit impedance
- IEEE Std C57.12.00 — transformer impedance tolerance
6. Validation cases
Hand-calculated cases run on every change. See Validation.
7. Known issues and changes
See the Changelog. Try the tool: Transformer Secondary Short-Circuit.