Methods / Cable Check
How RokBench checks this

Cable Check

What the check does, the formulas behind it, and what it deliberately leaves out.

1. What this check does

For a cable you have already chosen, RokBench computes the load current, compares the design current per set with the cable's allowable ampacity, and estimates the running and motor-starting voltage drop along the cable. It reports what does not hold up and why. It does not select a cable, although it may point to the smallest size in the same cable family that would pass.

2. Inputs used

3. Formulas and assumptions

Three-phase I = P / (√3 · V · PF · η) I = S / (√3 · V) Single-phase I = P / (V · PF · η) I = S / V HP P = HP × 745.7 W Design current per set Id = I × k / N k = 1.25 for motor and continuous loads, 1.0 otherwise; N = parallel sets Voltage drop ΔV = c · I · (L / 1000) · (R cos φ + X sin φ) / N c = √3 (three-phase, V line-to-line) or 2 (single-phase) R, X in Ω per 1000 ft per conductor; L in ft ΔV% = ΔV / V × 100 Starting same formula with I = multiple × I and φ from the starting PF

4. What is NOT checked

5. Reference standards

Pointers only; consult the edition adopted by your authority having jurisdiction.

6. Validation cases

Hand-calculated cases run on every change. Published textbook cases will be listed on the Validation page.

7. Known issues and changes

See the Changelog. Try the tool: Cable Check.

Screening toolfor licensed professionals. Not an engineering service. See Disclaimer.