Methods / Cable Check
How RokBench checks this
Cable Check
What the check does, the formulas behind it, and what it deliberately leaves out.
1. What this check does
For a cable you have already chosen, RokBench computes the load current, compares the design current per set with the cable's allowable ampacity, and estimates the running and motor-starting voltage drop along the cable. It reports what does not hold up and why. It does not select a cable, although it may point to the smallest size in the same cable family that would pass.
2. Inputs used
- Load as amperes, kW, HP or kVA; system voltage; single- or three-phase; power factor; efficiency (kW, HP).
- Load class: motor, continuous or non-continuous.
- Cable family and size, number of parallel sets, length, installation method and ampacity temperature column.
- Optional: a combined ampacity correction factor, system frequency, motor starting method, starting current multiple and starting power factor, voltage drop limits.
3. Formulas and assumptions
Three-phase I = P / (√3 · V · PF · η) I = S / (√3 · V)
Single-phase I = P / (V · PF · η) I = S / V
HP P = HP × 745.7 W
Design current per set Id = I × k / N
k = 1.25 for motor and continuous loads, 1.0 otherwise; N = parallel sets
Voltage drop ΔV = c · I · (L / 1000) · (R cos φ + X sin φ) / N
c = √3 (three-phase, V line-to-line) or 2 (single-phase)
R, X in Ω per 1000 ft per conductor; L in ft
ΔV% = ΔV / V × 100
Starting same formula with I = multiple × I and φ from the starting PF
- R, X and ampacity come from the cable library, which is built from manufacturer data sheets. The source is cited with every result. Rows still under source review are flagged.
- R is the AC resistance at the temperature stated in the data (typically the conductor rating). No further temperature adjustment is made, which is conservative for lightly loaded cables.
- X is scaled in proportion to frequency when the system frequency differs from the data.
- The voltage drop formula is the common approximate form, accurate for the small angle between sending and receiving voltages found in feeder and branch circuits.
- No correction for ambient temperature or grouping is applied unless you enter a correction factor.
- If you do not set voltage drop limits, a default limit is applied and shown with the result. Set the limits your project criteria require.
4. What is NOT checked
- Upstream voltage drop and source impedance. Starting drop is the cable drop only, not the voltage at the motor terminals.
- Harmonics, phase imbalance, neutral current and cable heating from non-sinusoidal loads.
- Short-circuit withstand, overcurrent protection and coordination.
- Termination temperature limits beyond an informational note.
- Conduit fill, tray fill, pulling tension and bending radius.
5. Reference standards
Pointers only; consult the edition adopted by your authority having jurisdiction.
- NEC 2023 430.6(A)(1), 430.22 — motor full-load current and conductor sizing
- NEC 2023 215.2(A)(1), 310.14, 310.15 — feeder sizing, ampacity and correction
- NEC 2023 310.10(G) — conductors in parallel
- NEC 2023 110.14(C) — termination temperature
- NEC 2023 210.19(A) Informational Note No. 4, 215.2(A)(2) Informational Note No. 2 — voltage drop recommendations
6. Validation cases
Hand-calculated cases run on every change. Published textbook cases will be listed on the Validation page.
7. Known issues and changes
See the Changelog. Try the tool: Cable Check.